Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the acf domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/webchecker3/web-checker3.net/public_html/hokuyo-aut/faq/wp-includes/functions.php on line 6121

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the better-wp-security domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/webchecker3/web-checker3.net/public_html/hokuyo-aut/faq/wp-includes/functions.php on line 6121
IN入力/OUT出力のPLCへの接続方法 | よくあるご質問 | 光データ装置、センサ、自動ドアなどの専門メーカー 北陽電機株式会社
よくあるご質問
FAQ
光データ伝送装置

IN入力/OUT出力のPLCへの接続方法

IN入力及びOUT出力をPLCに接続したいのですがどうすればいいですか。

NPNトランジスタ出力タイプですのでPLCの入出力はシンクタイプを接続します。
伝送装置のOUT出力をPLCの入力に、伝送装置のIN入力をPLCの出力に接続して伝送装置のCOMとPLCのマイナスCOMを接続してください。
伝送装置のCOMは電源のマイナスと内部で接続されています。